Below are instructions on how to adjust the Tekmar 279 control to address the building's heating characteristics and complaints.
Condition/complaint: If it is always hot inside building when it is cold or warm outside lower room temperature
Menu-> adjust-> room arrow up or down
Condition/complaint: If at warm weather people are comfortable but at cold weather they are not you need to change the BOILER DESIGN PERCENTAGE.
Menu-> adjust-> scroll. More percentage equals more heat when it is cold. Change increments of 5%. Wait 1 day for result.
Condition/complaint: When people are uncomfortable at warm weather outside but comfortable when it is cold then change indoor design temperature.
Less DESIGN TEMPERATURE is less heat, higher temperature is more heat at warm weather. CHANGE 5F at the time. Wait for 1 day for results.